Started By
Message

re: OT Electrician advice needed: running 110v off of 220v line

Posted on 7/7/21 at 3:38 pm to
Posted by TheHarahanian
Actually not Harahan as of 6/2023
Member since May 2017
19496 posts
Posted on 7/7/21 at 3:38 pm to
You’ll need some 8 gauge ball bearings and gauze tape.

Posted by Korkstand
Member since Nov 2003
28703 posts
Posted on 7/7/21 at 3:38 pm to
quote:

none of my house wiring has ever caused a fire. So far.
You're hired!
Posted by Obtuse1
Westside Bodymore Yo
Member since Sep 2016
25566 posts
Posted on 7/7/21 at 3:42 pm to
quote:

just an EE


quote:

110V


quote:

220V


Come on man.
Posted by Unobtanium
Baton Rouge
Member since Nov 2009
1592 posts
Posted on 7/7/21 at 3:43 pm to
With all due respect, you can't afford me!

But I do, on occasion, work for beer and boudin (after the job is done of course).
Posted by Unobtanium
Baton Rouge
Member since Nov 2009
1592 posts
Posted on 7/7/21 at 3:46 pm to
Varies with the tap setting on the substation transformer. Could be as low as 220, as high as 240.
Posted by CarRamrod
Spurbury, VT
Member since Dec 2006
57426 posts
Posted on 7/7/21 at 3:48 pm to
quote:

OT Electrician advice needed: running 110v off of 220v line


Yeah, don't do it.
I built a brewery control box that has 50amps in and controls a 23 amp 240v heating element and a 15 amp 120v outlet.

It can be done.
Posted by Obtuse1
Westside Bodymore Yo
Member since Sep 2016
25566 posts
Posted on 7/7/21 at 3:54 pm to
quote:

Varies with the tap setting on the substation transformer. Could be as low as 220, as high as 240.


If you got your degree before 1967 I will accept 110v and 220v as standard. Otherwise, it is not correct when speaking of the nominal standard and you know this man.
Posted by Unobtanium
Baton Rouge
Member since Nov 2009
1592 posts
Posted on 7/7/21 at 3:55 pm to
Custom made control box with what I assume are properly sized conductors and circuit protection =/= jury rigged wiring behind a wall.
Posted by Unobtanium
Baton Rouge
Member since Nov 2009
1592 posts
Posted on 7/7/21 at 4:03 pm to
1980, and my statement regarding tap changers stands.
Also depends on distance from substation as well. As well as load on that particular distribution leg.

220 - 240 is a perfectly acceptable range, as is 110 - 120. This is what I know, man. No device except a voltmeter cares about the difference, and no one but another engineer or an attorney would argue the point. So which are you?

ETA - Obtuse1, I will concede your point if you join me in helping convince OP to follow code and not burn his house down.

Also ETA - I have learned not to argue with lawyers. I only do it as a hobby while they do it for a living.
This post was edited on 7/7/21 at 4:19 pm
Posted by EA6B
TX
Member since Dec 2012
14754 posts
Posted on 7/7/21 at 4:18 pm to
quote:

Disclosure - not an electrician, just an EE. But I have lot of hands-on experience and none of my house wiring has ever caused a fire. So far.


It is always amusing to look at appliances, and see that adherence to the electrical code ends where the power cord enters the appliance, and standard engineering design takes over. For example a clothes dryer or electric range will have 4x #6 power cord externally, but transition to #14 wire internally going to the heating elements. The engineer has determined that for the needed internal wire length #14 is sufficient for the I*2R loss, but outside the unit the electrical code has to be complied with. I recently got a home standby generator, the electrician ran #2 wire the 18” from the meter base to the transfer switch as required by electrical code wire tables. I told the guy that from a engineering point of view # 10 wire would work perfectly fine, he assumed I was nuts.
Posted by td1
Baton Rouge
Member since Oct 2015
2827 posts
Posted on 7/7/21 at 4:19 pm to
The correct way would be to run a new 120V circuit to where you need the new outlet, or to tie into an existing 120V circuit near where the outlet needs to go. An electrician will be able to check if you can add the outlet to a nearby circuit or if you will need a new run.

The Oven circuit needs to be a dedicated circuit. The NEC will let you run a range and a oven on the same circuit, provided they do not exceed the circuit's rating. Not all municipalities will allow that though.

The sub panel thing won't fly bc it is very doubtful that the existing wiring has the capacity to remain compliant in running both the oven and the new branch circuit.

If you just want to blow money, they could probably put in a sufficiently sized run / sub panel.

I asked an electrician friend, he said to see 210.19, so I did, his explanation made more sense than the shite below:


210.19 Conductors — Minimum Ampacity and Size.
(A) Branch Circuits Not More Than 600 Volts.
Informational Note No. 1: See 310.15 for ampacity ratings of
conductors.
Informational Note No. 2: See Part II of Article 430 for mini-
mum rating of motor branch-circuit conductors.
Informational Note No. 3: See 310.15(A)(3) for temperature
limitation of conductors.
Informational Note No. 4: Conductors for branch circuits as
defined in Article 100, sized to prevent a voltage drop exceeding
3 percent at the farthest outlet of power, heating, and lighting
loads, or combinations of such loads, and where the maximum
total voltage drop on both feeders and branch circuits to the
farthest outlet does not exceed 5 percent, provide reasonable
efficiency of operation. See Informational Note No. 2 of
215.2(A)(1) for voltage drop on feeder conductors.
(1) General. Branch-circuit conductors shall have an ampacity
not less than the maximum load to be served. Conductors shall

N210.19 ARTICLE 210 — BRANCH CIRCUITS
70 –62 NATIONAL ELECTRICAL CODE 2017 Edition
be sized to carry not less than the larger of 210.19(A)(1)(a)
or (b).
(a) Where a branch circuit supplies continuous loads or
any combination of continuous and noncontinuous loads, the
minimum branch-circuit conductor size shall have an allowable
ampacity not less than the noncontinuous load plus
125 percent of the continuous load.
(b) The minimum branch-circuit conductor size shall
have an allowable ampacity not less than the maximum load to
be served after the application of any adjustment or correction
factors.
Exception: If the assembly, including the overcurrent devices protecting
the branch circuit(s), is listed for operation at 100 percent of its rating,
the allowable ampacity of the branch-circuit conductors shall be permit-
ted to be not less than the sum of the continuous load plus the noncon-
tinuous load.
(2) Branch Circuits with More than One Receptacle. Conduc-
tors of branch circuits supplying more than one receptacle for
cord-and-plug-connected portable loads shall have an ampacity
of not less than the rating of the branch circuit.
(3) Household Ranges and Cooking Appliances. Branchcircuit conductors supplying household ranges, wall-mounted
ovens, counter-mounted cooking units, and other household
cooking appliances shall have an ampacity not less than the
rating of the branch circuit and not less than the maximum
load to be served. For ranges of 83
/4 kW or more rating, the
minimum branch-circuit rating shall be 40 amperes.
Exception No. 1: Conductors tapped from a 50-ampere branch circuit
supplying electric ranges, wall-mounted electric ovens, and countermounted electric cooking units shall have an ampacity of not less than
20 amperes and shall be suf?cient for the load to be served. These tap
conductors include any conductors that are a part of the leads supplied
with the appliance that are smaller than the branch-circuit conductors.
The taps shall not be longer than necessary for servicing the appliance.
Exception No. 2: The neutral conductor of a 3-wire branch circuit
supplying a household electric range, a wall-mounted oven, or a
counter-mounted cooking unit shall be permitted to be smaller than the
ungrounded conductors where the maximum demand of a range of
8
3
/4-kW or more rating has been calculated according to Column C of
Table 220.55, but such conductor shall have an ampacity of not less
than 70 percent of the branch-circuit rating and shall not be smaller
than 10 AWG.
(4) Other Loads. Branch-circuit conductors that supply loads
other than those specified in 210.3 and other than cooking
appliances as covered in 210.19(A)(3) shall have an ampacity
sufficient for the loads served and shall not be smaller than
14 AWG.
Exception No. 1: Tap conductors shall have an ampacity suf?cient for
the load served. In addition, they shall have an ampacity of not less
than 15 for circuits rated less than 40 amperes and not less than 20 for
circuits rated at 40 or 50 amperes and only where these tap conductors
supply any of the following loads:
(a) Individual lampholders or luminaires with taps extending
not longer than 450 mm (18 in.) beyond any portion of the lampholder
or luminaire
(b) A luminaire having tap conductors as provided in 410.117
(c) Individual outlets, other than receptacle outlets, with taps
not over 450 mm (18 in.) long
(d) Infrared lamp industrial heating appliances
(e) Nonheating leads of deicing and snow-melting cables and
mats
Exception No. 2: Fixture wires and ?exible cords shall be permitted to be
smaller than 14 AWG as permitted by 240.5.


Posted by Floyd Dawg
Silver Creek, GA
Member since Jul 2018
3898 posts
Posted on 7/7/21 at 4:51 pm to
Step down transformer
Posted by Cracker
in a box
Member since Nov 2009
17669 posts
Posted on 7/7/21 at 4:57 pm to
220 is just 2 110 lines
Posted by kywildcatfanone
Wildcat Country!
Member since Oct 2012
118943 posts
Posted on 7/7/21 at 5:44 pm to
220, 221, whatever it takes
Posted by Penrod
Member since Jan 2011
39108 posts
Posted on 7/7/21 at 5:59 pm to
I don’t think you can meet code either way. Using the 220 volt circuit to feed a distribution panel, from which you feed both the 110 volt receptacle and the 220 volt oven is a good idea, but I doubt you would be able to get the access to that panel required by code.

The other way you suggested is surely against code, though I could not cite why.

I think you should run another 110 volt circuit from your existing panel or from a nearby circuit.

ETA: Unobtainium is correct when he says
quote:

If this is an older home then the original oven circuit only has two 'hots' and a ground conductor and no neutral. Using a ground wire as a normal current-carrying conductor is a big no-no.


BTW, I’m an EE as well.
This post was edited on 7/7/21 at 6:11 pm
Posted by Penrod
Member since Jan 2011
39108 posts
Posted on 7/7/21 at 6:01 pm to
quote:

Split the amperage in half and add two breakers at the panel. Put one hot into each breaker and run that to your 220 plug for oven. Put a wire nut in that box and run one of your hots to the 110 plug.

This is the way it’s done in El Salvador. What could go wrong?
Posted by Penrod
Member since Jan 2011
39108 posts
Posted on 7/7/21 at 6:04 pm to
quote:

couldn't I just change the single gang receptacle to a dual-gang, then use an adapter like this? It has a 15a fuse built-in:

I doubt it. Wouldn’t that be hidden by the oven? Surely that would not meet code requirements for a circuit interrupter. Even if it’s accessible it is probably not listed as suitable for that service.
Posted by Shanegolang
Denham Springs, La
Member since Sep 2015
3409 posts
Posted on 7/7/21 at 6:19 pm to
quote:

I know nothing about electricity beyond V=IR


Ohms law isn't gonna do this guy any good!

OP- Buy a good fire extinguisher before you take on this science project!
Posted by ArHog
Muss is a coward
Member since Jan 2008
32950 posts
Posted on 7/7/21 at 6:20 pm to
quote:

I think you should run another 110 volt circuit from your existing panel or from a nearby circuit


Correct answer.

I've been a master electrician for 30 years.
Posted by Meauxjeaux
98836 posts including my alters
Member since Jun 2005
39858 posts
Posted on 7/7/21 at 6:29 pm to
quote:

I think you should run another 110 volt circuit from your existing panel or from a nearby circuit


Correct answer.

I've been a master electrician for 30 years.


Funny I’m doing almost the same thing.

Next question, if I tap off a nearby 120v circuit that does not have an existing gfci outlet, does this one need to be gfci.

Our scenario: going from electric to a gas range and the only thing back there is the 240v.
first pageprev pagePage 3 of 4Next pagelast page

Back to top
logoFollow TigerDroppings for LSU Football News
Follow us on Twitter, Facebook and Instagram to get the latest updates on LSU Football and Recruiting.

FacebookTwitterInstagram