I'm by far no electrician. I need to run wire 120ft, 50 amp, 110v. What size wire to do I need to use? Thanks for help
Posted by McCringleberryy
Member since Dec 2012
4315 posts
Posted on 4/23/16 at 7:46 am to
6
Posted by djangochained
Gardere
Member since Jul 2013
19185 posts
Posted on 4/23/16 at 7:49 am to
16 gauged
Posted by BeerMoney
Baton Rouge
Member since Jul 2012
9008 posts
Posted on 4/23/16 at 7:50 am to
indoor/outdoor? In the attic?
Posted by Kajungee
South ,Section 6 Row N
Member since Mar 2004
17033 posts
Posted on 4/23/16 at 7:52 am to
Based on your question, not knowing the ratings of your terminations # 6 awg THHN copper. If the terminations are rated 75C or higher #8 awg cu should be sufficient.

However I am more curious what you need a 50 amp, 120 volt circuit for ? Something does not sound right. And good luck finding a 50 amp, 1 pole breaker.
Posted by Tino
:yawn:
Member since Dec 2004
86225 posts
Posted on 4/23/16 at 7:55 am to
That's the question I wanted to ask as well
Posted by LCA131
Home of the Fake Sig lines
Member since Feb 2008
77695 posts
Posted on 4/23/16 at 7:56 am to
quote:

However I am more curious what you need a 50 amp, 120 volt circuit for ? Something does not sound right. And good luck finding a 50 amp, 1 pole breaker.


My first thought as well. KGee, I am sure you know the tech. side of things more completely than I do but I thought that to be a LOT of amps for 120v.
Posted by LuckySo-n-So
Member since Jul 2005
22754 posts
Posted on 4/23/16 at 8:07 am to
I've been an electrician for 20 years and have never run a 110v 50 amp circuit.
Posted by DeoreDX
Member since Oct 2010
4376 posts
Posted on 4/23/16 at 8:10 am to
quote:

However I am more curious what you need a 50 amp, 120 volt circuit for ? Something does not sound right. And good luck finding a 50 amp, 1 pole breaker.


I've seen someone redneck up a 120v only sub panel with xx/2 instead of xx/3. Black to one leg, white to neutral, bare to ground, and a pig tail from one leg of the sub to the other leg. Used only single pole breakers.

I saw a lot of interesting rednecked up shite working summers with my dad as an electrician.
This post was edited on 4/23/16 at 8:11 am
Posted by ItFliesItDies
NO MAN's LAND
Member since Apr 2011
1246 posts
Posted on 4/23/16 at 8:26 am to
Then I'm assuming wrong, must be double breaker and 220v
Posted by muttenstein
Member since Oct 2012
3214 posts
Posted on 4/23/16 at 8:28 am to
220, 221, whatever it takes.
Posted by DrSteveBrule
Baton Rouge
Member since Sep 2009
12545 posts
Posted on 4/23/16 at 8:30 am to
quote:

Based on your question, not knowing the ratings of your terminations # 6 awg THHN copper. If the terminations are rated 75C or higher #8 awg cu should be sufficient.


#8 would be fine in that instance per NEC, but it depends on the length of the run. If voltage drop is an issue then #6 is needed

quote:

Then I'm assuming wrong, must be double breaker and 220v


50/2 breaker and sizing as mentioned by others for conductor, either a 3/4" conduit or 1", I forget what the NEC says. Probably need a #10 ground wire as well.
This post was edited on 4/23/16 at 8:33 am
Posted by mdomingue
Lafayette, LA
Member since Nov 2010
48595 posts
Posted on 4/23/16 at 8:32 am to
quote:

16 gauged


I worked in a DIY type store (Handy City/Handy Dan if anybody recalls that store) back in my college days. Had a couple of guys come in wanting to by 18 gauge lamp cord for an 4500 watt industrial heater. I wouldn't sell it to them, but they lingered around and cut it themselves when I was with another customer. Not sure if they burned their shop down or not. I kinda knew the guys, they had worked for my stepdad when he had a small hot shot business.
Posted by mdomingue
Lafayette, LA
Member since Nov 2010
48595 posts
Posted on 4/23/16 at 8:52 am to
quote:

If voltage drop is an issue then #6 is needed


At 120 ft full load .8 PF you're looking at 8 V vs 5 V drop fro 8 to 6. 8 is probably sufficient. If the price difference is small enough, go with 6.

quote:

Probably need a #10 ground wire as well


Probably right, typically one size smaller but no need to worry about that if he goes with one of these:

8/3 NM-B W/G

6/3 NM-B W/G


Posted by 1mic
Through the coulee
Member since Nov 2014
168 posts
Posted on 4/23/16 at 8:53 am to
RVs use 120v 50amp service
Posted by retired trucker
midwest
Member since Feb 2015
5093 posts
Posted on 4/23/16 at 8:56 am to
if he wants a fire...
Posted by Milk
central
Member since May 2010
1308 posts
Posted on 4/23/16 at 9:05 am to
You would probably get better advice if you told everyone what you are wiring. The fact that you are not sure if its a single or double pole breaker you need means your in over your head.
first pageprev pagePage 1 of 1Next pagelast page
refresh

Back to top
logoFollow TigerDroppings for LSU Football News
Follow us on X, Facebook and Instagram to get the latest updates on LSU Football and Recruiting.

FacebookXInstagram