re: Transfer switch for generator

Posted on 7/7/23 at 1:30 pm to
Posted by cdhorn28
Member since Sep 2016
248 posts
Posted on 7/7/23 at 1:30 pm to
That's what has me confused, neither have a 200amp breaker or a "main" breaker to shut power off to the house, as far as I see. I'm going to post some pics this evening when I get home. Maybe I'm just a clown, but I'll triple check. I mean is it even possible not to have 1 breaker that shuts everything off?
Posted by kengel2
Team Gun
Member since Mar 2004
31085 posts
Posted on 7/7/23 at 2:42 pm to
quote:

I mean is it even possible not to have 1 breaker that shuts everything off?



Yes, 6 passes of the hand is the rule. Although a lot of jurisdictions are making people put a single means of disconnect now depending on what year NEC they are adopting.

quote:

The “six breaker throw rule” was a requirement in the National Electrical Code that a service must have have a main disconnect that shuts off all power and it cannot take more than six switch throws to do it
Posted by HondaBigRed
5th Ward
Member since Jun 2023
115 posts
Posted on 7/12/23 at 3:12 pm to
Bump on this tread. Any recommendations for an electrician in the BR/Ascension area that can install an interlock switch and 30A outlet?
Posted by Butta
Zachary
Member since Dec 2012
236 posts
Posted on 7/12/23 at 3:25 pm to
quote:

Any recommendations for an electrician in the BR/Ascension area that can install an interlock switch and 30A outlet?


I used Buffalo Electric in Baker
Posted by TygerB8
Youngsville
Member since Jul 2005
1353 posts
Posted on 7/12/23 at 5:36 pm to
Look into an interlock and you will be good. Link here LINK
Posted by bee Rye
New orleans
Member since Jan 2006
33985 posts
Posted on 7/12/23 at 6:32 pm to
Post a picture of the inside of your exterior panel and I’ll tell you what you need to buy
Posted by Nawlens Gator
louisiana
Member since Sep 2005
5850 posts
Posted on 7/12/23 at 8:38 pm to


quote:

I mean is it even possible not to have 1 breaker that shuts everything off?


I had to replace my outside meter box for one that had a 200 amp breaker below the Entergy meter so I could disconnect from Entergy before switching to generator power.

Posted by LSUDad
Still on the move
Member since May 2004
59045 posts
Posted on 7/12/23 at 9:42 pm to
quote:

Bump on this tread. Any recommendations for an electrician in the BR/Ascension area that can install an interlock switch and 30A outlet


Call John, he taught electrical at the Trade School. Great guy.

This post was edited on 7/18/23 at 2:21 am