NOLA S&WB turbine knocked offline for 2 hours

Posted on 6/10/20 at 5:14 pm
Posted by Geauxld Finger
Baton Rouge
Member since Jan 2005
32628 posts
Posted on 6/10/20 at 5:14 pm
LINK

can we take the s&wb out of city control? they're lying, corrupt, and totally worthless

if anything above a tropical depression heads here id bet getting the frick out

quote:

Turbine 4, which provides about a third of the power needed by most of the S&WB's pumps, went down about 8:52 a.m., Korban said. That was after some areas were already reporting significant rainfall and flooding, but the loss of the turbine kept the S&WB from pumping out the water as quickly as it otherwise would have, Korban said.


quote:

Somebody asked me ... over the weekend, what is my biggest worry. And I said 'T4 tripping or being damaged where it can't operate because that is our go-to power generation equipment,' " Korban said. "So, we have redundancy in the system. It's not the redundancy that we need; it's not the redundancy we had a year ago. We are going into this season with a more fragile system and a less redundant system than ever before."



Posted by tgrbaitn08
Member since Dec 2007
148031 posts
Posted on 6/10/20 at 5:16 pm to
quote:


if anything above a tropical depression heads here id bet getting the frick out



That’s a lot different than what happened today.

The city is much better protected from a storm surge than it is for a rain event.
Posted by AbitaFan08
Boston, MA
Member since Apr 2008
27902 posts
Posted on 6/10/20 at 5:16 pm to
Only two hours?
Posted by Northshoretiger87
Member since Apr 2016
4957 posts
Posted on 6/10/20 at 5:18 pm to
I dont know how much confidence you give me by using “much better.” Much better from what starting point?
This post was edited on 6/10/20 at 5:20 pm
Posted by tgrbaitn08
Member since Dec 2007
148031 posts
Posted on 6/10/20 at 5:21 pm to
quote:

With the loss of 20 megawatt turbine 4 during today's storm, I would guess a lot of people are wondering: What S&WB drainage pumps get powered by 25 cycle power. We're going to look at the east bank west of the Industrial Canal. That's because all pumps in New Orleans East and all but two smaller pumps and two diesel pumps on the west bank run on Entergy power. Also, that's where the flooding reports were concentrated today.

For reference drainage basins for each station can be found at the link in the comments.

DPS 1 25 cycle: Pumps A, B, C, D, E, V1, V2, totalling 4550 cubic feet per second (cfs)

DPS 1 60 cycle: Pumps F, G totalling (2415 cfs)

DPS 2 25 cycle: Pumps A, B, C, D (totalling 3100 cfs)

DPS 2 60 cycle: None

DPS 3 25 cycle: Pumps A, B, C, D, E (totaling 4100 cfs)

DPS 3 60 cycle: None

DPS 4 25 cycle: Pumps C, D, E (totaling 3000 cfs)

DPS 4 60 cycle: Pumps 1, 2 (totaling 640 cfs)

DPS 5 25 cycle: Pumps A, B (totaling 1100 cfs)

DPS 5 60 cycle: Pumps 1, 2 (totaling 584 cfs)

DPS 6 25 cycle: Pumps A, B, C, D, E, F, G (totaling 6125 cfs)

DPS 6 60 cycle: Pumps H, I, V1, V2, V3, V4 (totaling 3200 cfs)

DPS 7 25 cycle: Pumps A, C (totaling 1550 cfs)

DPS 7 60 cycle: Pump D (totaling 1000 cfs)

DPS 12 25 cycle: Pump D (totaling 1000 cfs)

DPS 12 60 cycle: None

DPS 17 25 cycle: None

DPS 17 60 cycle: Pumps A, D (totaling 210 cfs)

DPS 19 25 cycle: None

DPS 19 60 cycle: Pumps H1, H2, H3, V1, V2 (totaling 3920 cfs)

DPS I-10 25 cycle: None

DPS I-10 60 cycle: Pumps 1, 2, 3 (totaling 750 cfs)

DPS Oleander 25 cycle: None

DPS Oleander 60 cycle: Pumps 1, 2, 3 (totaling 99 cfs)

DPS Pritchard 25 cycle: None

DPS Pritchard 60 cycle: Pumps 1, 2 (totaling 250 cfs)

The 60 cycle pumps are run off of Entergy. I checked the Entergy outage map during the storm today and didn't see any major outages across the city.

The standard way S&WB runs their 25 cycle pumps is to feed one pump in each of stations 1, 2, 3, 4, 6, and 7 off of frequency changers, which ultimately get their power from Entergy. Usually, it is pump "C" in those stations. The rest of the 25 cycle power would come from the turbines at the Carrollton Plant.

With the loss of 20 megawatt (MW) turbine 5 in December, they have hopefully been running things in novel configurations. This could mean running more 25 cycle pumps off of frequency changers, which would insulate somewhat against a turbine loss as happened today. But no matter what, the loss of up to 20 MW from turbine 4 tripping out would hurt big time. And it looks like it did, with stations 4, 3, and 12 appearing to take it on the chin based on the flood report map.

It would deepen the amount of water in the areas already flooded, and it would push water outward into areas which didn't have water. Then, overall, it would take far longer to drain those areas after power was restored.

Now, I read that Executive Director Ghassan Korban said they didn't know which pumps went out due to the loss of T4. That's arse-covering BS. S&WB collects data on every pump and every turbine every second of every day. It would take literally about ten minutes to check exactly which pumps went down at the same time as the turbine tripped.
Posted by Geauxld Finger
Baton Rouge
Member since Jan 2005
32628 posts
Posted on 6/10/20 at 5:22 pm to
sustained rainfall and a power outage would flood nola. but hey, no storm surge at least
Posted by Gee Grenouille
Member since Jul 2018
8543 posts
Posted on 6/10/20 at 5:43 pm to
How is it that we can keep TGENs running for months at a time and they never shut off offshore? I hate to assume it's just gross incompetence. I always assume there are just some details I am not privy to.