Electrical Question

Posted on 7/4/25 at 10:57 pm
Posted by mcpotiger
Missouri
Member since Mar 2005
8812 posts
Posted on 7/4/25 at 10:57 pm
GFCI outlet just started tripping. Reset it and it trips again with nothing plugged in. I changed the outlet and the other one I know that is on that circuit. Still tripping . I will reset it and it will trip within a few seconds. It’s in the hall bathroom. Any suggestions.
Posted by Zappas Stache
Utility Muffin Research Kitchen
Member since Apr 2009
42200 posts
Posted on 7/4/25 at 11:03 pm to
Does it trip with nothing plugged in to it?
Posted by mcpotiger
Missouri
Member since Mar 2005
8812 posts
Posted on 7/4/25 at 11:05 pm to
Yes it does . I replaced it but still doing the same thing .
Posted by Zappas Stache
Utility Muffin Research Kitchen
Member since Apr 2009
42200 posts
Posted on 7/4/25 at 11:16 pm to
I would replace the breaker next
Posted by mcpotiger
Missouri
Member since Mar 2005
8812 posts
Posted on 7/4/25 at 11:22 pm to
Yea. Thats what I was thinking. Thanks
Posted by LsuFan_1955
Slidell, La
Member since Jul 2013
1908 posts
Posted on 7/5/25 at 1:08 am to
While you are changing the breaker, check that all the neutrals and ground screws in the distribution panel are tight as well.
This post was edited on 7/5/25 at 1:09 am
Posted by mcpotiger
Missouri
Member since Mar 2005
8812 posts
Posted on 7/5/25 at 1:30 pm to
Replaced breaker. Still tripping outlet with no load. Guess I’ll call in a professional.
Posted by grifterfad
Mobile, Al
Member since Jun 2013
219 posts
Posted on 7/5/25 at 1:39 pm to
There's probably more than two outlets downstream from that GFI. I would check all the bathrooms, the garage, and any outside outlets.
Posted by ItzMe1972
Member since Dec 2013
12110 posts
Posted on 7/5/25 at 1:49 pm to
Check for outside outlet that may be corroded or wet from rain.
This post was edited on 7/5/25 at 1:50 pm
Posted by Motorboat
At the camp
Member since Oct 2007
23875 posts
Posted on 7/5/25 at 2:11 pm to
quote:

There's probably more than two outlets downstream from that GFI. I would check all the bathrooms, the garage, and any outside outlets


This. Had the same problem. Was a downstream gfi across the house. Reset it and all is well. Check everywhere for the red light.
Posted by mcpotiger
Missouri
Member since Mar 2005
8812 posts
Posted on 7/5/25 at 5:49 pm to
Thanks fellars.. found the culprit. Outside on back patio . Never use it but It’s on the circuit and it’s ancient. It was corroded and a mess. Replaced it and all is well. Appreciate the direction. Enjoy your weekend
Posted by LsuFan_1955
Slidell, La
Member since Jul 2013
1908 posts
Posted on 7/5/25 at 6:02 pm to
Good call, this is sounding like you truely had a Ground Fault issue.
This post was edited on 7/5/25 at 6:04 pm