Help Needed from HVAC Professionals

Older five ton unit. Working fine yesterday mid morning. Returned late last night and it was 86° inside the house with the inside fan blowing. Outside unit only buzzes/hums. Changed the capacitor with no change to buzzing/humming.
Fan motor, compressor or something else?
TIA


Shepherd
LSU Fan
Member since Nov 2009
2921 posts

re: Help Needed from HVAC Professionals
Pan full of water?


Replies (0)
Replies (0)
00
ItzMe1972
Member since Dec 2013
9237 posts

re: Help Needed from HVAC Professionals
Do you know if the compressor is starting?

Do you have fuses on the panel outside?

You need to check voltages on the contactor/relay. Power in? Power out?


diablo blanco
LSU Fan
Oakdale, Louisiana
Member since Dec 2007
1076 posts

re: Help Needed from HVAC Professionals
Thanks, all!
Checked the wrong breaker box inside.
(Older house with two main panels.)
Compressor and outside unit fired up after I reset the tripped breaker.