re: Running Central A/C On A Standard Size Generator

Posted on 2/18/21 at 8:05 pm to
Posted by dbeck
Member since Nov 2014
29454 posts
Posted on 2/18/21 at 8:05 pm to
quote:

Make sure to get one that is the correct size for your unit.

They don't make them that big.
Posted by Jopete
New Iberia
Member since Apr 2019
373 posts
Posted on 2/18/21 at 8:08 pm to
i install soft starts on my window units at the camp. it's easier on the generator when the compressor kicks in.
Posted by ScoobyDont
Member since Sep 2016
816 posts
Posted on 2/18/21 at 8:09 pm to
I believe they make a Magnum.
This post was edited on 2/18/21 at 9:31 pm
Posted by Obtuse1
Westside Bodymore Yo
Member since Sep 2016
26177 posts
Posted on 2/18/21 at 8:16 pm to
quote:

They don't make them that big.


A 4-ton unit is going to pull about 20 amps or 4800w at 240v, not a problem to find a portable gen to run that. The problem is the starting load will be roughly 5 times that.